How to test a surge arrester?

06 May.,2024

 

How to Diagnose High Voltage Surge Arrester

Surge arresters play a key role in protecting electrical devices and equipment in high-voltage electrical substations. Like other devices, they must be periodically diagnosed. The most common method is visual inspection: checking that the arrester has no visible external mechanical damage.

You can find more information on our web, so please take a look.

However, an arrester with no visible external damage can sometimes suffer internal damage. As a result, it may not be able to protect against a surge or overvoltage. Doble Engineering makes monitors for detecting leakage currents in surge arresters and got together with Fluke Europe. We used Fluke’s handheld thermal imaging cameras to create a reliable diagnostic solution to this challenge.

Testing high-voltage surge arresters

The IEC60099-5 international standard includes an overview of methods used for diagnosing high-voltage surge arresters. We developed the LCM500 Leakage Current Monitor precisely for this purpose. It performs non-invasive diagnostics of varistor-type surge arresters (with metal-oxide blocks) during operation.

This instrument measures the quality of the metal oxide blocks to help manage the risk of failure. Specifically, it uses IEC60099-5 method B2, analyzing the leakage current’s 3rd harmonic with harmonics compensation in the grid voltage. According to the international standard, this is the most reliable method of diagnosing high-voltage surge arresters during operation.

We tested the LCM500 at a 110kV/6kV overhead power line substation. The station, which has two transformer fields, is fitted with valve-type surge arresters. Table 1 (below) shows the measurements we took from the LCM500. Valve-type arresters should give low total values of leakage current, and current values of same-type arresters should be similar. As shown, though, the L2 phase leakage current was considerably higher than for the other two phases. That suggested that the L2 phase arrester might be damaged.

Confirming our results with a thermal imager

We then wanted to make sure thermal imaging cameras could help us to verify the findings of the LCM500. The Fluke Ti450 Pro Infrared Camera seemed like the right choice, since it can capture (and visualize) very small temperature differences. This particular camera is extremely sensitive and gives accurate, sharp onscreen images. It does this even when the surge arresters are high up or far away. Examples of thermal images from the field study are shown in below. The temperature difference Delta-T of 10°C in the arrester’s upper part shows additional local heating.

This approach of measuring the leakage current using the LCM500 and then using the Ti450 Pro infrared camera clearly showed damage in the L2 phase surge arrester. Our tests also confirmed that the LCM500 can effectively assess the technical condition of high-voltage, valve-type surge arresters. We concluded that this complementary method of verifying the possible damage to surge arresters provided the reliable diagnostics solution we were looking for.

*Please note that the Fluke Ti450 Pro Infrared Camera has been updated to the Ti480 since the original publication of this case study.

Related resources

Techniques & Methodologies For Health Assessment Of ...

Lightning / Surge Arresters are specialised devices that protect electrical installations and equipment from unpredictable electrical surges caused by internal events like electrical faults, switching, short circuits, etc. and external events like lightning impulses, lightning strokes, etc.

Over the last few decades, Lightning / Surge Arresters have evolved from using Silicon Carbide to Zinc Oxide (ZnO). While ZnO offers superior protection, Arresters with ZnO Blocks often tend to fail violently once their degradation starts.

Some of the common factors that lead to the degradation of ZnO Blocks include lightning strikes, electrical surges, moisture buildup, environmental contamination and the gradual ageing of the Arresters.

As a result of the aforementioned factors, the effective resistance of the Arresters significantly reduce leading to an increase in the Leakage Current (It) and thereby I2R losses.

Continuous I2R losses generate more heat and accelerate ageing that in turn decreases the Arresters’ effective resistance ultimately leading to their complete failure.

Understanding The Electrical Equivalent Circuit of Lightning / Surge Arresters

Understanding the Electrical Equivalent Circuit of Arresters is pivotal to monitor their health for optimal performance. In the above illustration:

R: Resistive Component

C: Capacitive Component

Ir: Resistive Current                                                                   

Ic: Capacitive Current

It: Total Leakage Current

1: High Voltage

2: Connection to the ground as well as the location of the current measurement.

A pertinent point that needs to be kept in mind is that while the capacitive component of the leakage current remains almost constant, it is the resistive leakage current that is primarily responsible for heating up the Arresters’ ZnO Blocks.

With increased heat dissipation, the Arresters’ Blocks can become thermally unstable and lead to thermal runaway and maybe explosions. Regular monitoring of the leakage current flowing in the ZnO Blocks therefore becomes paramount.

Techniques Used

When it comes to evaluating the healthiness of Lightning / Surge Arresters, there are three key techniques that are widely used.

With competitive price and timely delivery, Hengfeng sincerely hope to be your supplier and partner.

1. Tan Delta Measurement

With a degradation of the Arrester, the Ir value increases that results in the increase of the angle δ finally resulting in an increased value of the Tan δ. Monitoring the trend of the Tan δ value forms the basis of the Tan Delta measurement technique.

2. Insulation Resistance Test / Leakage Current Test on DC

In this technique, an Insulation Resistance Test or Leakage Current Test is conducted on the DC that eliminates the the Ic value and only the Ir value get reflected in the measurement results. This measurement is less accurate in providing a true picture on the healthiness of the Lightning / Surge Arresters.

3. Third Harmonic Resistive Leakage Current Measurement

In this technique, the leakage current flowing through the earth wire is measured with the help of a specialised Clamp-on Ammeter. From the leakage current, the third order harmonics are calculated from which the third order resistive component is derived.

This is the most preferred technique as being an online measurement, it does not require any shut down.

Measuring The Resistive Leakage Current Or Power Loss

As per standard IEC 60099-5 amendment 1, there are 8 different methods of measuring the resistive leakage current or power loss in the AC Leakage Current Measurement technique. These 8 methods are categorised as A1, A2, A3, A4, B1, B2, B3 and C.

While the A1 to A4 methods describe the direct measurement of the resistive leakage current, the B1 to B3 methods describe the indirect determination of resistive component by means of harmonic analysis of the leakage current and the C method explains the direct determination of power loss.

Please feel free to contact us for a more detailed explanation of each method mentioned in IEC 60099-5. IEC 60099-5 clause 6.5 highlights a detailed comparison of the various on-site Leakage Current Measurement methods. Here is a quick snapshot of the same for ready reference.

It is apparent from the above table that B1 and B2 methods deliver the best results compared to other methods.  

However, the B2 method gives a more accurate health analysis of the Arrester as compared to the B1 method since the effect / error of harmonics present in the system voltage gets compensated in the B2 method only.

We can therefore conclude that the B2 method is the best method to follow when assessing the Arresters’ heath.

SCOPE SA30i+

SCOPE SA 30i+ is a state-of-the-art wireless Leakage Current Analyser designed for assessing the residual life of Metal Oxide Surge Arresters.

SA 30i+ accurately measures and directly displays the values of the Total Leakage Current and Third Harmonic Resistive Leakage Current along with the harmonic compensation as per IEC 60099-5-B2.

Designed to work under the hostile electrostatic noise found in live EHV switchyards up to 765 kV, SCOPE’s SA 30i+ seamlessly provides Corrected Resistive Leakage Current after applying necessary correction factors for changes in the system voltage and temperature. For more information, please visit https://www.scopetnm.com/test-and-measurements/item/75-sa-30i or write to us at marketing@scopetnm.com.

Share this:

Like

Loading...

If you are looking for more details, kindly visit RESISTIVE CURRENT TESTER FOR ZNO ARRESTER.